B for group h 1 h 2 or continue reading detailing concrete masonry fire walls.
2 hour fire wall concrete block.
For example for an 8 in.
These wall assembly files are used for planning and estimation purposes for many ul wall types such as fire rated wall assemblies.
1 groupfire resistance rating hr a b e h 4 i r 1 r 2 u3a f 1 h 3b h 5 m s 13 h 1 h 24b f 2 s 2 r 3 r 42 a walls shall not be less than 2 hour fire resistance rated where separating buildings of type ii or v construction.
2 ncma tek 7 1c table 1 fire resistance rating period of concrete masonry assemblies refs.
4 or c 331 ref.
Concrete masonry fire resistance.
13 mm a 1 in.
Standard northwest block wall ratings.
The fire resistance rating of concrete masonry walls depends on the type of aggregate used in the units.
Table 1 required fire wall fire resistance ratings ref.
A 2 hour rating can be achieved by a wall with an equivalent thickness of as little as 3 1 5 inches when expanded slag or pumice is used or 4 1 2 inches when siliceous gravel is used as the aggregate.
Mm for fi re resistance rating hoursa b concrete masonry unitc 4 33 4 31 2 31 4 3 23 4 21 2 21 4 2 13 4 11 2 11 4 1 3 4 1 2.
Fire barrier walls are typically constructed of drywall or gypsum board partitions with wood or metal framed studs.
Linear interpolation from table 721 3 2 of the florida building code for exposed finish block mix 55 limestone 45 siliceous aggregates.
These blocks while allowing for safe means of egress and fire rating should no longer be looked at as just normal grey cmu.
Some of the above listed shapes are non stock items.
Concrete masonry noncombustible constructionis a.
Penetrations penetrations through fire walls such as for pipes and cables must be.
Westbrook block is a proud producer of underwriters laboratories ul approved fire rated cmu in both light weight and normal weight densities in 2 3 and 4 hour configurations.
25 mm thickness measured perpendicular to the face of the wall of ceramic fiber in the joint can be used in walls with fire resistance ratings up to 3 hours while a 2 in.
Walls composed of hollow concrete masonry units having a nominal thickness of 8 inches or greater and having a fire resistance rating of at least 2 hours shall be classified as 4 hours when the hollow spaces are completely filled with perlite or vermiculite grout or a material such as expanded.
203 mm limestone aggregate concrete masonry wall with a maximum control joint width of in.
51 mm thickness can be used.
Usg provides resources here for our ul wall assemblies for seamless integration into any construction project.